Rockford Industrial Area Revival Project - Moderated newsgroup   >   Welding and Fabricating   >   Honeywell S7800A1001 display for 7800 series controls

Honeywell S7800A1001 display for 7800 series controls


Honeywell S7800A1001 display for 7800 series controls


From: Daniel Bentley
Subject Honeywell S7800A1001 display for 7800 series controls
Provides current status of burner sequence, timing information, hold information and lockout information,
as well as selectable or preemptive messages.
• Communication interface capability with Switchover to ModBus programmable.
• First-out annunciation and system diagnostics provided by 2 row by 20 column Vacuum Fluorescent Display (VFD).
• S7800A1001 offers "Call Service" (Business Card)programmable message displayed when system lockout occurs.
• S7800A1001 series 5 and greater has selectable ModBus Feature.
• Local or remote annunciation of operation and fault information.
• First out expanded annunciation with 24 limit and interlock LEDs enhances keyboard display module information. Display can be Programmed to customize the expanded annunciator messages to the system. Provides burner controller data.
13 Vdc peak fullwave rectified ( +20/-15%).
4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep
123 mm wide x 73 mm high x 23 mm deep
Approvals, Underwriters Laboratories Inc
Component Recognized, File No. MP268; Guide No. MCCZ.
Approvals, Canadian Standards Association
Certified, File No. LR95329-3.
Approvals, Federal Communications Commission
FCC Part 15, Class B, Emissions.
Approvals, Industrial Risk Insurers
Contact: DBentley@rockford-industrial.com (Daniel Bentley)